Overview
The VITP-MW3A microwave presence detector provides
automatic control of lighting loads via the VitessePlus
marshalling box.
The VITP-MW3A detects movement using a highly
sensitive microwave detector. This works by emitting low
power microwave signals and measuring the reflections as
the signals bounce off moving objects.
Functioning as a presence detector, the unit can turn lights
on when a room is occupied and off when the room is
empty. When used with a non-dimming LCM settings allow
lights to be turned off in response to ambient daylight. If a
dimming LCM is used the detector can be set-up to
implement a maintained illuminance (constant light)
system.
The VITP-MW3A has a unique adjustable sensor head that
allows the area of detection to be optimised for the
application.
All functionality is fully programmable using an IR handset.
Features
Back features
VitessePlus microwave presence detector
Product Guide
Retaining Spring
Retaining Spring
Two VitessePlus
RJ45 Connections
Microwave Sensor
Detects movement within the unit’s detection range,
allowing load control in response to changes in occupancy.
IR Receiver
Receives control and programming commands from an
IR (infrared) handset.
Light Level Sensor
Measures the overall light level in the detection area
Status LEDs
The LED flashes Red to indicate the following:
RJ45 Connections
Two RJ45 connections for CAT5 patch leads.
Walk Test LED active
when movement is detected
Valid setting received
VITP-MW3A
Front features
Sensor Lens
which covers...
Microwave Sensor
IR Receiver
Light Level Sensor
Status LEDs
Mounting Bezel
Vue de la page 0
1 2 3 4 5 6 7 8

Résumé du contenu

Page 1 - VITP-MW3A

Overview The VITP-MW3A microwave presence detector provides automatic control of lighting loads via the VitessePlus marshalling box. The VITP-MW3A

Page 2 - Detection diagrams

2 When movement is detected the detector sends a signal to the VitessePlus marshalling box (LCM). The LCM is programmed to either, turn on the load

Page 3 - Installation

3 Choosing a Suitable Location The VITP-MW3A is designed to be ceiling mounted and must satisfy the following criteria:  Avoid positioning the uni

Page 4 - Fault finding

4 When power is applied to the unit, the load will turn on immediately. Set the timeout to 10 seconds (commissioning only) vacate the room or remain

Page 5 - Basic programming - UHS5

5 Basic programming - UHS5 Parameter Name Default Value 0 1 2 3 UHS5 Handset Graphics Description Button Activation On / Raise On R

Page 6 - Advanced programming

6 Parameter Name Default Value Range / Options Description UHS5 UNLCDHS Detector Parameters Walk Test LED Off On or Off When set to On th

Page 7

7 Advanced programming Lux switching on all channels covered by one sensor (non-dimming LCMs only) Lux on level (Switch level on) 9 1 to 9 For a hi

Page 8 - Technical data

8 Dimensions See diagrams opposite Weight 0.1kg Supply Voltage 12VDC Power consumption On 447mW, Off 400mW Temperature -10ºC to 50ºC Humidity