1. Description and Operation
Section Contents Page
1 Description and operation 1
2 Dimensions 2
3 Wiring 5
4
Setup
6
5
Programming
9
6
Detection pattern diagrams
11
7
Fault finding
11
8
Specification
12
9
Part numbers
12
The MWS5 series of miniature microwave presence
detectors provide automatic control of lighting loads
with optional manual control. The unit comes
complete with a selection of fixing clips, allowing
unobtrusive flush mounting of the sensor head into
ceiling tiles or on to solid surfaces. It has been
designed so that it can be used for ceiling mounted
or wall mounted applications. As microwave
radiation penetrates plastic and glass, this unit has
been specifically designed to be mounted inside a
luminaire. If you wish to use this type of control
outside a luminaire housing, please use the
―SA‖ (Standalone) version.
Three models are available: non-dimming MWS5,
direct dim DD and analogue dim AD, all of which
will switch incandescent, fluorescent and compact
fluorescent lighting. The direct dim (DD) variant
controls DSI or DALI digital dimming ballasts whilst
the analogue dim (AD) variant controls 1-10V
analogue dimming ballasts.
The unit detects movement using a microwave
sensor and turns the load on. When an area is no
longer occupied the load will switch off after an
adjustable time out period has elapsed.
*for lux, time and sensitivity
Feature
MWS5
(Non-dimming)
MWS5-DD
Direct Dim
MWS5-AD
Analogue Dim
Up to 8m microwave sensing
3 mounting options
Lux sensor
Absence detection
Presence detection
Infrared remote setting
Infrared user handset
Push button adjustment*
Relay output
Dimming output
Absence switch input
Up/down switch input
Contents
Miniature Ceiling Mounted Microwave Presence Detector
Product Guide
MWS5
Vue de la page 0
1 2 3 4 5 6 ... 11 12

Résumé du contenu

Page 1 - Product Guide

page 1. Description and Operation Section Contents Page 1 Description and operation 1 2 Dimensions 2 3 Wiring 5 4 Setup 6 5 Programming 9

Page 2

page 10 4 Dimming Channel 2 functions -DD & -AD only (factory default in brackets): 4.1 Light level Maintained illuminance level (adjustable

Page 3

page 11 6. Detection Patterns 7. Fault Finding LOAD DOES NOT COME ON Check to see if the live supply to the circuit is good. Strap across the L an

Page 4

page 12 LOAD 6 Amps fluorescent and incandescent lighting. 3 Amps compact fluorescent lighting. 3 Amps low energy lighting. 3 Amps low voltage lighti

Page 5 - 3. Wiring

page 2 2. Dimensions & Mounting options The product is supplied as two part numbers, and consists of the following parts:-  Power Supply Unit

Page 6 - 4. Setup

page 3 Flush mounting the sensor head using the flush mount bracket The product can be mounted into a flat panel of a luminaire using the flush moun

Page 7 - 4. Setup cont

page 4 2. Dimensions & Mounting options cont. Flush fitting the sensor head behind a diffuser using the flange bracket Flush fitting the sensor

Page 8

page 5 3. Wiring Wire the products as shown in the diagrams below. All switches are optional with presence detection, but a switch will be required

Page 9 - 5. Programming

page 6 1. Connect the power supply via the terminal block on the power supply unit as shown overleaf. Live supply to the L terminal, Neutral to the

Page 10 - 5. Programming (continued)

page 7 Settings adjustment:-  On initial power up, the factory set default settings are:-  Presence Detection mode.  Time = 20 minutes.  Lux

Page 11 - 7. Fault Finding

page 8 Push button adjustment Time, Lux and Sensitivity  Press and hold either button for at least 5 seconds then release: one of the LED’s positi

Page 12 - 8. Specification

page 9 5. Programming All the following functions can be programmed using the remote control DD-LCDHS handset: 1. Detector Parameters (factory d